Wuhan Rising Electric Co., Ltd.

Manufacturer from China
Active Member
6 Years
Home / Products / CT PT Testing Equipment /

RSCTP Ct Pt Analyzer For Current Transformer And Voltage Transformer

Contact Now
Wuhan Rising Electric Co., Ltd.
City:wuhan
Province/State:hubei
Country/Region:china
Contact Person:MrJason
Contact Now

RSCTP Ct Pt Analyzer For Current Transformer And Voltage Transformer

Ask Latest Price
Brand Name :RISING
Model Number :RSCTP
Certification :ISO CE
Place of Origin :China
MOQ :1 SET
Payment Terms :L/C, L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :500 SET PER Month
Packaging Details :Wooden package
Operational Power Supply :AC220V±20V, 50~60Hz
Excitation Output Current :0~5A (20 A)
Single Machine Output Current of Transformation Ratio Test :0~600 A
CT Ratio measurement Range :5~10000A/5A(5000A/1A)
PT Ratio Measurement Range :1~500KV
Operating Temperature :-10℃~+40℃
Relative Humidity :<90RH%
Overall Dimension :400 *200 * 260(mm)
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

RSCTP CT PT Testing Instrument Analyzer for Current Transformer and Voltage Transformer

Product Description

CT/PT ANALYZER is mainly used for field testing of Current Transformer and Voltage Transformer. The test items mainly include excitation characteristic, transformation ratio, polarity, Degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current. Adopt LCD, self-equipped minitype printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.

Feature/Function/Parameters
I. Current Transformer (CT) II. Voltage Transformer (PT)
1. Magnetization Curve 1. Excitation Characteristic Test
2. Transformation Ratio Test 2. Transformation Ratio Test
3. Polarity 3. Polarity
4.5% and 10% error curve 4. Withstand Test of Power Frequency Alternating Current
5. Current Injecting 5. Degauss
6. Degauss 6. Calculation of Knee Point Value
7. Withstand Test of Power Frequency Alternating Current
8. Automatic Calculation of Excitation Knee Point Value

Main Technical Parameters
Operational Power Supply: AC220V±20V, 50~60Hz
Equipment Power Supply Output Waveform: Sine Wave
Single Machine Output Voltage of Excitation Characteristic: 0~1000V
Excitation Output Current: 0~5A (20 A)
Single Machine Output Current of Transformation Ratio Test 0~600 A
CT ratio measurement range 5~10000A/5A(5000A/1A)
PT ratio measurement range 1~500KV
Error: ≤0.5%(0.2%*Reading+0.3%*Range)
Operating Temperature: -10℃~+40℃
Relative Humidity: <90RH%
Altitude ≤1000m
Overall Dimension(Length×Width×Height): 400 *200 * 260(mm)
Weight: ≤23 Kg