Wuhan Rising Electric Co., Ltd.

Manufacturer from China
Active Member
6 Years
Home / Products / Relay Protection Device /

Six Phase Microcomputer 20 Times Relay Protection Device

Contact Now
Wuhan Rising Electric Co., Ltd.
City:wuhan
Province/State:hubei
Country/Region:china
Contact Person:MrJason
Contact Now

Six Phase Microcomputer 20 Times Relay Protection Device

Ask Latest Price
Brand Name :RISING
Model Number :RS1200
Certification :ISO CE
Place of Origin :China
MOQ :1 SET
Payment Terms :L/C, L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :500 SET PER Month
Packaging Details :Wooden package
Power :Electric
Phase :6 Phase
Warranty :1 Year
Color :White and Blue
Number of harmonic :1-20 times
Weight :35KG
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

RS1200 6Phase Relay Protection Device Microcomputer Relay Protection Tester

Product Description

Wuhan Rising Electric.,CO is specialized in manufacturing all grades of transformer testing equipment, load no-load transformer characteristic tester, automatic ratio groups of test instrument, transformer winding deformation tester, power frequency testing transformer, automatic anti jamming tester, series resonance test device, partial discharge detection device, insulating oil dielectric strength tester, etc With abundant of experience and professional team we have exported our products to many countries and regions all over the world, especially the Middle East area, Asian area. Eastern Europe, etc. Also our products are widely recognized and trusted by users.

Rated Parameters

—AC output current

When six-phase current is output, each phase outputs (effective value) 0-30A with output accuracy 0.2 class

When three-phase current is output, each phase outputs (effective value) 0-60A

Six-phase paralleling output current (effective value) 0-180A

Long-time allowable work value of phase current (effective value) 10A

Maximum output power of phase current 300VA

Maximum output power in the case of the Maximum output of six-phase paralleling current 1,000VA

Allowable working hours in the case of the maximum output of six-phase paralleling current 10s

Frequency range (fundamental wave) 0-1,000Hz

Number of harmonic 1-20 times

—DC output current

Output current 0-±10A/each phase output accuracy 0.5 class

Maximum output load voltage 20V

—AC output voltage

Phase output voltage (effective value) 0-120V output accuracy 0.2 class

Line output voltage (effective value) 0-240V

Phase voltage/line output voltage power 80VA/100VA

Frequency range (fundamental wave) 0-1,000Hz

Number of harmonic 1-20 times

—DC output voltage

Phase output voltage amplitude 0-±160V with output accuracy 0.5 class

Line output voltage amplitude 0-±320V

Phase voltage/line output voltage power 70VA/140VA

—Switching value

8-route switching value input

Idle contact 1-20mA, 24V

Electric potential contact connects "0": 0-+6V;“1”:+11V - +250V

4 pairs of switching value output DC: 220 V/0.2A;AC:220V/0.5A

-Time measurement range

0.1ms-9999s, measurement accuracy<0.1mS

Inquiry Cart 0